TP-6515 2/21 13Section 1 Specifications
Section 1 Specifications
1.1 Introduction
The generator set specification sheets provide specific
generator and engine information. Refer to the spec
sheet for data not supplied in this manual. Consult the
generator set service manual, engine operation manual,
and engine service manual for additional specifications.
Obtain copies of the latest spec sheets, manuals,
diagrams, and drawings from your local distributor/
dealer.
1.2 Generator
The generator uses Kohler’s unique PowerBoost
voltage regulation system, which provides instant
response to load changes.
PowerBoost ensures reliable motor starting and
consistent voltage levels. PowerBoost utilizes a
voltage excitation system that employs a winding
independent of the main output windings to provide
excitation voltage.
1.3 Engine
The generator set has a four-cycle, twin cylinder, air-
cooled Kohler engine. The engine operates on clean-
burning natural gas or propane (LP) vapor. Engine
features include:
Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability
under all operating conditions.
Dependable, maintenance-free electronic ignition.
Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LP vapor (and vice-
versa) while maintaining CARB emission
certification.
Digital spark advance optimizes ignition timing for the
selected fuel. (12 - 18 kW models)
1.4 Advanced Digital Control
The generator set is equipped with the Kohler
ADC-RES Advanced Digital Control. Controller
features include the following:
Compact controller
Integrally mounted to the generator set
LED display:
Engine runtime, hours
AC voltage
Frequency (Hz)
Battery voltage
Crank cycle status
Setup information
Application software version
LED display communicates faults:
High battery voltage
High engine temperature
Low battery voltage
Low oil pressure
Overcrank safety
Overfrequency
Overspeed
Overvoltage
Underfrequency
Undervoltage
Membrane keypad for configuration and adjustment
Password-protected user access to menus
Voltage, gain, and speed adjustment
System configuration (system voltage/frequency
settings and generator set model)
Remote two-wire start/stop capability
Digital isochronous governor to maintain steady-
state speed at all loads
Digital voltage regulation: ±1.5% RMS no-load to
full-load
Automatic start for programmed cranking cycle
Master control switch mounted on the junction box:
Run/Off-Reset/Auto
Upgradeable application software