What to do if the breaker will not close in RUN on my Kohler 20RCA Portable Generator?
- FfarleyjudithAug 18, 2025
If the breaker won't close in RUN on your Kohler Portable Generator, it could be due to: another breaker being closed (stop the other generator set), auto-discovery not being complete (initiate auto-discovery by ensuring this generator is in RUN mode and the other is stopped with the controller in OFF mode), or bus sensing not being connected correctly (check wiring between both generators and the Automatic Paralleling Module).