70 Part Number STH063 9/17
Suction Pressure Low Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist” on
page 53.
Discharge Pressure
Discharge pressure is too low, and is affecting suction
pressure, refer to “” on page 66
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-OEM components in system
Improper water supply over evaporator refer to
“Water System Checklist” on page 54.
Loss of heat transfer from tubing on back side of
evaporator
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
TXV starving
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.