Remove the cover of the processing unit
and check the status of the LEDs.
Power supply:
Does green LED 8 light up?
Overheating:
Does red LED 6 not light up?
Function:
Does green LED 7 flash (1/s)?
Data reception RX:
Does red LED 4 flash?
Data transmission TX:
Does green LED 3 flash?
1. Contact the manufacturer.
1. Check the power supply (12-24 VDC).
Temperature exceeds 105 °C:
1. Install the flowmeter away from the delivery line
at a cooler point.
Processing unit malfunction:
1. Contact the manufacturer.
No data reception from the processing unit:
1. Check the cabling.
2. Ensure that the Modbus master is transmitting.
Processing unit does not respond:
1. Check the Modbus address.
2. Check the cabling.
3. Check the terminating resistor (120 Ω).
4. Check the transmission rate (baud rate).