9 Trouble-shooting
63 of 68
Calio
1157.821/04-EN
Error value
Possible cause Remedy
7)
E06 Voltage error Verify that the supply voltage matches the data on the name
plate.
Measure the mains voltage.
E08 Motor fault
Incorrect rotor angle due to external
flow or other causes, e.g. blocked
rotor.
De-energise the pump for 1minute; then re-energise it.
If the faults/alarms have not been cleared, have the motor
checked by KSBService.
E11 Broken wire of temperature sensor
(NTC) in the motor
Have it checked by KSBService.
E12 Firmware not compatible Carry out a firmware update.
E13 No pump model stored. Pump stops. Carry out a firmware update.
Enter pump size as indicated on the name plate.
I10 Broken wire of 0-10V control signal
(Pump is not stopped. Can be set via
KSB ServiceTool)
Check the analog 0-10V control signal.
I14 For dual pumps both pumps are
programmed as "left pump". Pumps
keep running.
Carry out firmware update for "right pump".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB Calio and is the answer not in the manual?

KSB Calio Specifications

General IconGeneral
Max Operating Pressure10 bar
Connection SizeDN 32
MaterialStainless steel
Applicationsheating, cooling, industrial processes
Connection TypeFlanged
Power Supply1~230 V, 50/60 Hz / 3~400 V, 50/60 Hz

Related product manuals