12) INVERTER ON KEY: Enable Inverter Operation
CAUTION!
The LEDs mounted on the mimic flow chart represent the various power paths and
current UPS operational status.
Mains indicator
Rectifier in Normal Operation
Input mains voltage or frequency out of normal range
Battery indicator
Battery Normal, but discharging and powering the load
Battery End of Discharge pre-warning, Battery abnormal (high
or low voltage, Absent or Polarity Reversed), charger
abnormal
Battery and Converter Normal, Battery charging.
Bypass indicator
Bypass not available, out of normal range, Static bypass
switch short or broken fault, bypass switch wiring fault, bypass
over current
Bypass Normal, load not on bypass
Inverter indicator
Inverter Normal and powering the load
Inverter failed, Inverter IGBT bridge direct conduct
protection, Inverter Thyristor short or broken fault, over
load or Parallel Overload, Feedback protection
Output indicator
Ffault indicator