Instruction Manual of
Programmable Power Controller (KT-PPC)
REV
1.6E
PAGE : 23 OF 25
Doc No: TIR9402-30-D01
210*297(mm) KTE CO., LTD TI-06(R0)
7. DIAGNOSTIC & TROUBLES AND CORRECTING MEASURES
As soon as you power on this product, it starts self-diagnosis function and show you the result, so it
help you not to perform a failure due to the initial system errors.
When you need to perform self-diagnosis function, just push the 'RESET' button, then it will show you
the diagnosis results. (Note : Do not push 'RESET' button while the system operate). Error messages and
trouble shooting methods of diagnosis results are explained as follows.
No
Error Message
Probable causes
Corrective measures
1
E E P r
EEPROM Fault
EEPROM (IC13) Fault
EEPROM (IC13) Exchange
Internal Circuit Fault
Circuit check or Exchange
2
E r r P
Internal Voltage Fault (+5V)
Internal Overvoltage
Inspect & Adjust (VR1)
Power Line Short or Broken
Power Line Check
Internal Circuit Fault
Circuit check or Exchange
3
E P5
Internal Voltage Fault (+5V)
Internal Overvoltage
Inspect & Adjust (VR1)
Power Line Short or Broken
Power Line Check
Internal Circuit Fault
Circuit check or Exchange
4
E P 1 2
Internal Voltage Fault (+12V)
Internal Overvoltage
Inspect & Adjust (VR2)
Power Line Short or Broken
Power Line Check
Internal Circuit Fault
Circuit check or Exchange
5
E - 1 2
Internal Voltage Fault (-12V)
Internal Overvoltage
Inspect & Adjust (VR3,4)
Power Line Short or Broken
Power Line Check
Internal Circuit Fault
Circuit check or Exchange
6
G E n X
GEN, No.X (X : 1,2,3)
Analog Input Fault
Analog Input(AnX) Short or Broken
ANx Line Check
External Power Detector Fault
Power Detector Check
Internal Circuit Fault
Circuit check or Exchange
7
G E X X
GEN, No.XX (XX :12,13,23)
Analog Input Fault
Analog Input(AnXX) Short or Broken
ANx,x Line Check
External Power Detector Fault
Power Detector Check
Internal Circuit Fault
Circuit check or Exchange
8
G 1 2 3
GEN, NO.1,2,3
Analog Input Fault
Analog Input(An1,2,3) Short or Broken
AN1,2,3 Line Check
External Power Detector Fault
Power Detector Check
Internal Circuit Fault
Circuit check or Exchange
9
I n X X
Channel No.XX (148)
Internal Input Fault
Internal Input IC Fault
Defective IC Exchange
Internal Input Line Short or Broken
Board check or Exchange
Internal Circuit Fault
Circuit check or Exchange
10
o u X X
Channel No.XX (140)
Internal Output Fault
Internal Output IC Fault
Defective IC Exchange
Internal Output Line Short or Broken
Board check or Exchange
Internal Circuit Fault
Circuit check or Exchange
REMARK : NO6, 7, 8 Analog input Fault
- If the analog input becomes less than 2.4mA, an alarm occurs about 5 seconds later.