Digital UnderVoltage Relay (GDR-D01) User's Manual V1.10
Kyongbo Electronics Co., Ltd.
Ÿ System Config. ▶ T/S Output ▶ T/S 1 ▶ 3.DLY Setting
It is a category that can add to the recovery delay time on the recovery.
This menu is only applied when it is in Self Mode in the above 2. RST Setting, and
is not applied if it is in Manual Mode.
If DLY is set to 0.00, it recovers within 40ms, and if you want the recovery within
100ms, set it to be 0.06.
It can be set in the units of 0.01Sec from 0.00 to 60.00, and it recovers with the
error ratio of ±35ms if under 100ms, and the error ratio of ±5% if 100ms or more.
6.2.5.3 System Config. ▶ Password Setting
It is a category to change the Password Setting, and the password is set as 4
digits using the numbers from 0 to 9.
Select 3.Password category in Config., then the following screen appears.
From this screen, input new password, and press ENTER ( ) Key, then the screen
to input the new password again appears as follows.
From this screen, input password again, and press ENTER ( ) Key, then the
following screen appears, and it converts to the upper menu.
If you don't want to change password in Password Screen, press Key, then it will
exit from this menu and convert to the upper menu.