2 Installation
2.1 Mounting the TPSD
When mounting the TPSD in ANY configuration, consider the size and weight of the unit. The wall, rack, and/or
floor must be able to support the weight of the unit as well as an additional safety factor. Verify the method of
mounting and the weight of the TPSD, using Tables 1, 2, and 3. The location chosen for the charger should be
within an ambient temperature range of 32 to 122˚F (0 to 50˚C) with a non-condensing relative humidity no
higher than 95%. The TPSD should be mounted in an area free of explosive materials and away from drips and
splatter. The TPSD utilizes convection cooling so a clearance of at least 6in (152mm) of free air must be
maintained on the top, bottom and both sides for cooling air. Maintain 36in (914mm) or more of clearance at
the front of the charger in order to allow for operation and maintenance.
Case Number
Cable Entry
Mounting
AC Input DC Output
4B
Right Left
19/23” Rack, Wall/Floor
(see Fig. 1a and 1b)
4
Right Left
19/23” Rack, Wall/Floor
(see Fig. 1a and 1b)
9
Top Right Top Left
23/30” Rack, Wall/Floor
(see Fig. 1a and 1b)
72
Right / Bottom Bottom Floor
44
Left Right Floor
Table 3 - Available mounting methods for each of the TPSD case sizes
Figure 2 - Mounting configurations
(4B Case top view)
Figure 1 - Mounting configurations
(4B Case front view)