3.3.1 Base plan, static load and weights
Picture 3 – Base plan
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady
and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Power (kVA) 60 80 100 125 160
Weight w/o batteries (kg) 250 300 320 360 380
Static load w/o batteries (kg/m
2
) 490 590 630 710 750
Weight with batteries (kg) 800 850 - - -
Static load with batteries (kg/m
2
) 1570 1670 - - -