5.3.1 Display of alarms history
All the events are recorded in the alarms history.
UPS STATUS
HISTORY
HISTORY: xxx/yyy
Alarm code Date/time
The first event shown is the latest one in order of time; a new event makes all the other events
automatically shift one position, clearing the oldest event.
The quantity of stored events is displayed on the first line (xxx/yyy), which contains the data
currently displayed (position in the list) and the total number of stored data (maximum number equal
to 500) respectively. An asterisk indicates the automatic reset of the alarm.
HISTORY: 001/015
Latest event stored (in order of time)
E.g.: automatic reset of alarm “A3 –
BOOSTER STOPPED
A3 * 26-10-10 20:05
HISTORY: 002/015
Immediately prior event
E.g.: alarm “A3 – BOOSTER STOPPED”
A3 26-10-10 19:45
HISTORY: 015/015
First event stored (in order of time)
A18 15-10-10 12:49