MUL41E-0610/06-2011 Page 13
8.2.4 - External second set point
In this case the actual set point is specifyd by one of the 2 set point (3238) and (3239). The final set point depends
on the status of the digital dry contact allocated to this function.
8.2.5 - External current 4/20mA offset
In this case the set point is set by one of the previous solution and can be adjust with an offset of +/- 1.0°C.
8.2.6 - C60 value
The CLIMATIC™ 60 receives the water set point from the DC60. If the set point read is different from the one
calculated by the CLIMATIC™ 60, the new set point is set by the DC60 during the actual zone. Each time the zone
is changing, the DC60 set point is overwritten by the CLIMATIC™ 60 set point.
8.2.7 - BMS value
The CLIMATIC™ 60 receives the water set point from the BMS. Refers to the “BMS” paragraph for more details.
The cooling and heating set points can be pre-specified according to the scheduling and can take different mode
for each schedule mode (A, B, C, D, and BMS).