CLIMATIC™ 60 AIRCOOLED CHILLERS
Page 18 MUL41E-0610/06-2011
10.2.3 - Fix delta P
The CLIMATIC™ 60 maintains a fix delta of pressure according to the transducers (in and out) on the pump. The
delta of pressure desired is customized in the menu (3375).
10.2.4 - Fix Out P
The CLIMATIC™ 60 maintains a fix out pressure according to the out transducer on the pump. The output pressure
desired is customized in the menu (3376).
10.3 - Settings
The different settings to adjust the flow control are available in the menu:
(3372): Type of flow control,
(3374): Delta of temperature desired on the evaporator water (Outlet - Inlet),
(3375): Delta of pressure desired on the water pump (Out - In),
(3376): Output pressure desired on the water pump (Out),
(3377): Minimum of flow on the evaporator water,
(3378): Maximum of flow on the evaporator water.