CLIMATIC™ 60 AIRCOOLED CHILLERS
Page 24 MUL41E-0610/06-2011
The compressor is subject to various operating time in order to prevent from damage operating.
The minimum ON time of the compressor is fixed to 1 minute,
The minimum OFF time of the compressor is fixed to 1 minute,
The minimum between 2 starts of the same compressor is fixed to 5 minutes.
13.3 - Settings
The different settings to configure the compressors are available in the menu:
(3331): Enable of the compressor(s) on the circuit 1
(3332): Enable of the compressor(s) on the circuit 2
(3335): Priority of the circuit rotation.