CLIMATIC™ 60 AIRCOOLED CHILLERS
Page 72 MUL41E-0610/06-2011
ALARM 001:
WATER EVAPORATOR, FLOW SWITCH CUT OFF
Description
The flow switch has detected a low water flow rate in the evaporator heat exchanger for more than 5 seconds
whereas the unit was enable.
Action
Immediate shut down of the complete unit.
Reset
Once the flow has been detected for 2 minutes, the alarm is automatically deleted. Up to 3 trips can occur during a
day and are saved in the alarm historic. The two first trips don’t give the alarm alert except if a trip is still present
during 1 hour, and are automatically reset every day at 6h00 am. The third trip activates the fault report and must
be manually reset.
Possible cause(s)
Problem with the pump control wiring,
Problem with the flow switch wiring,
Dirty or clogged water filter,
Wrong setting of the flow switch.
Remedies
Check the pump(s) connections,
Check the flow switch connections,
Clean the water filter,
Check the flow switch settings.