CLIMATIC™ 60 AIRCOOLED CHILLERS
MUL41E-0610/06-2011 Page 75
ALARM 025, 026, 027, 028:
WATER CONDENSER, OUT OF RANGE
Description
The water condenser temperature (Inlet or Outlet) measured by the probe is outside of the permitted range.
Alarm 025: ****************************************************************************************************
Alarm 026: ****************************************************************************************************
Alarm 027: ****************************************************************************************************
Alarm 028: ****************************************************************************************************
Action
Immediate shut down of the complete unit. The alarm is signalling 5 min after if the condenser temperature is still
out of range.
Reset
The alarm is automatically deleted once the temperature has reached the permitted operating range for 2min. After
a change over mode, these alarms are reset during 15min.
Possible cause(s)
Problem with wiring of probe,
Temperature probe failed.
Remedies
Check the connections of the probe,
Replace probe.