CLIMATIC™ 60 AIRCOOLED CHILLERS
Page 78 MUL41E-0610/06-2011
ALARM 043, 044:
PUMP CONDENSER, ELECTRICAL FAILURE
Description
The thermal magnetic circuit breaker protection of the condenser pump 1 or 2 has tripped for 5s, whereas the
pump was in demand for at least 5s.
Alarm 43: Thermal magnetic circuit breaker protection of the pump 1,
Alarm 44: Thermal magnetic circuit breaker protection of the pump 2.
Action
Case of single pump:
Immediate shut down of the pump and the unit.
The alarm is signalling.
Case of double pump:
Immediate shut down of the current pump and the compressor(s).
Time delay of 30s,
Start the second pump if possible (refers to the “PUMP CONDENSER MANAGMENENT paragraph)
The alarm is signalling.
Reset
These alarms are manually reset.
Possible cause(s)
Problem with wiring connection,
Circuit breaker wrong adjusted.
Remedies
Check the pump connections,
Adjust the circuit breaker.