CLIMATIC™ 60 AIRCOOLED CHILLERS
MUL41E-0610/06-2011 Page 83
ALARM 071, 072:
EXPANSION BOARD LINK, FAILURE
Description
The link between the expansion board(s) 1 or 2 and the CLIMATIC™ 60 is disconnected.
Alarm 71: The expansion board N°1 is disconnected from the CLIMATIC™ 60,
Alarm 72: The expansion board N°2 is disconnected from the CLIMATIC™ 60.
Action
Immediate shut down of the unit.
The alarm is signalling.
Reset
Once the communication is re-established for 30s, the alarm is automatically deleted. Up to 6 trips can occur during
a day and are saved in the alarm historic. The five first trips don’t give the alarm alert except if a trip is still present
during 1 hour, and are automatically reset every day at 6h00 am. The sixth trip activates the fault report and must
be manually reset.
Possible cause(s)
Problem with wiring connection,
Wrong expansion board address,
Expansion board damaged.
Remedies
Check the wiring connections,
Check the expansion board address (refers to the “FREE INPUT / OUTPUT” paragraph),
Replace the expansion board.