MUL41E-0610/06-2011 Page 89
ALARM 108:
POWER FACTOR CORRECTION, ELECTRICAL FAILURE
Description
The thermal magnetic circuit breaker protection of the capacitors (cos phi) has tripped for 5s.
Action
The alarm is signalling.
Reset
The alarm is manually reset.
Possible cause(s)
• Problem with wiring connection,
• Circuit breaker wrong adjusted.
Remedies
• Check the capacitor connection,
• Adjust the circuit breaker.