Page 92 MUL41E-0610/06-2011
ALARM 114, 214:
COMPRESSOR, ELECTRICAL FAILURE
Description
The thermal magnetic circuit breaker protection or the thermal motor protection of the compressor has tripped.
• Alarm 114: Thermal magnetic circuit breaker on the circuit 1,
• Alarm 214: Thermal magnetic circuit breaker on the circuit 2.
Action
Immediate shut down of the complete circuit. The alarm is signalling.
Reset
The alarm is manually reset.
Possible cause(s)
• Problem with wiring connection,
• Circuit breaker wrong adjusted,
• Compressor damage.
Remedies
• Check the wiring connection,
• Adjust the circuit breaker,
• Replace the compressor.