CONSOLE GRAPHIQUE KP07
VI. VI. CONTENT OF SCREENS
III.1. Summary
The water instruction is a variable which can be modified in "modification" mode. For a liquid cooler, the value
displayed or entered is read or copied respectively into the active instruction ("A" or "B" depending on the value
of the variable CHPCONS).
Where several KP01 cards are connected to the same KP07, the controller number can also be modified. On
all other screens, the controller number can only be read.
Date and time data can also be changed. Every 24 hrs, the console automatically reads the date and time on
the lowest JBUS address controller and sends this information to any other controllers connected to it.
III.2. Water output temperature curve
The monitoring frequency for the temperature of chilled water output (or hot water for a PAC) is 10 minutes,
over a complete 24 hour cycle. The console therefore memorises the last 144 values of the monitored variable.
Date and time
Presence of a
general alarm on
the machine
Water instruction
Temperature of chilled
water input (or hot water
for a PAC)
Temperature of chilled
water output (or hot water
for a PAC)
Number of controller
in communication
with display unit