23
Table 2. Energy Saving Set Points
The thermostat
default setting is
two period only.
To use four peri
ods, change the
appropriate setup
parameter.
Time Heating Cooling
Fan Setting
Occ1 70°F (21°C) 76°F (24°C) Auto
Unocc1 55°F (10°C) 85°F (29.5°C) Auto
Occ2
a
70°F (21°C) 76°F (24°C) Auto
Unocc2
a
62°F (17°C) 85°F (29.5°C) Auto
Energey Saving Default
Energy saving recommended set points for heating
and cooling can help save energy. The time and
temperatures reference in table 2 are
pre-programmed into the thermostat to achieve
energy savings.
Scroll to ENERGY SAVING DEFAULT; touch to
select. Read the message on the screen and to
continue, touch CONFIRM.
System Test Mode
After the thermostat has been installed and set-up,
the installer may run a system test function
(accessed through the installer settings menu), to
test all cooling, heating, Emergency Heating stages
and FAN outputs. Tests are available for Y1, Y2, W1,
W2, G, ECO and D. The test can be activate by
toggling the action to ON. The OB test can be toggle
between B and O.
Touching the OFF button next to the desired option
will change the status to ON and will enable the relay
for that terminal. Touching again will turn OFF the
relay. Touch the left arrow (<) to exit the system test
mode.