22
OS
HR/T
DS
AS
AS
HR/T
DPT
DIFS
RS
3
BAC
2
DADS
LDRP
CO2
RS
HR/T
6
5
4
PT1
PT2
1
OS
AS
FREE-COOLING 4
020S
5 x 4mm² 5 x 10mm²
4 x 1,5 mm²
4 x 2,5 mm²
+
6 x 1,5 mm²
4 x 4 mm²
+
6 x 1,5 mm²
4 x 6 mm²
+
6 x 1,5 mm²
4 x 6 mm²
+
7 x 1,5 mm²
7 x 1,5mm²
4 x 1,5mm² N/A
025S
5 x 6mm²
5 x 16mm²
030S
035S
3 x 25mm²+
2 x 16mm²
4 x 1,5 mm²
4 x 4 mm²
+
6 x 1,5 mm²
4 x 6 mm²
+
6 x 1,5 mm²
4 x 10 mm²
+
6 x 1,5 mm²
4 x 10 mm²
+
7 x 1,5 mm²
040S 5 x 10mm²
045S
5 x 16mm²
3 x 35mm²+
2 x 16mm²
055D
3 x 50mm²+
2 x 25mm²
4 x 1,5 mm²
(STD/HP1)
4 x 2,5 mm²
(HP1/HP2)
4 x 6 mm²
+
6 x 1,5 mm²
3 x 10
mm²+PE
+
6 x 1,5 mm²
4 x 16 mm²
+
6 x 1,5 mm²
4 x 16 mm²
+
7 x 1,5 mm²
4 x 1,5mm²
4 x 1,5mm²
070D
3 x 25mm²+
2 x 16mm²
3 x 70mm²+
2 x 35mm²
085D
100D
3 x 35mm²+
2 x 16mm²
3 x 95mm²+
2 x 50mm²
2 x (4 x 4mm²)
+ 10 x 1,5mm²
+ 6 x 1mm²
4 x 2,5 mm²
(STD/HP1)
2 x (4 x 1,5
mm²)
(HP1/HP2)
4 x 10 mm²
+
6 x 1,5 mm²
4 x 16 mm²
+
6 x 1,5 mm²
4 x 25 mm²
+
6 x 1,5 mm²
4 x 25 mm²
+
7 x 1,5 mm²
4 x 2,5mm²
2.- INSTALLATION
2.8.- ELECTRICAL CONNECTIONS
- BEFORE MAKING ANY ELECTRICAL CONNECTIONS, ENSURE THAT ALL CIRCUIT BREAKERS ARE OPEN.
- IN ORDER TO MAKE THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE UNIT.
Note: The length of all cables for connection with indoor unit must be less than 65 m.
To connect by installer
OUTDOOR
SECTION
Electrical
box
POWER SUPPLY
POWER SUPPLY
POWER
SUPPLY 1
POWER
SUPPLY WITH
E.H. 1’
CONNECTION
BETWEEN
OUTDOOR UNITS
FAN 2
BATERÍA ELÉCTRICA 3
EXHAUST
FAN 5
RETURN
FAN 6
STANDARD MEDIUM HIGH
MODULA-
TING