EasyManua.ls Logo

Lennox EDA - Using Humiditrol Comfort Adjust; Leak Testing, Evacuating, Charging; Insulating And Sealing The Unit; Other System Components

Lennox EDA
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
2.4.2. Leak Testing, Evacuating, Charging
1. Setthe3-waydivertingvalveactuatorshafttothecenter(evacuate)positionfor
leaktestingandevacuationasillustratedinthefollowinggure.IMPORTANT!
TheactuatorshaftmustbesetasdescribedtoallowtheHumiditroltoevacuate
morequickly.
2. Refertoinstructionsprovidedwiththeoutdoorunitforleaktesting,evacuating
andchargingprocedures
3. VerylittlechargeisrequiredfortheadditionalvolumeoftheHumiditrolunit.
Wheninnormalcooling,thecomponentswillallbeoccupiedbyvaporthathas
verylittleweight.Atmost(dependingonthemodel)anadditional1/4poundof
refrigerantmayberequired.
4. When shifting from dehumidify mode to cooling, or vice-versa, wait at least
10minutesforthesystemtoreachstableoperatingpressurebeforechecking
temperaturesandpressures,oradjustingrefrigerantcharge.
NOTE: Prior to starting the outdoor unit for charging, set the thermostat to call for
cooling (dehumidication OFF). It will take about 90 seconds for the 3-way
diverting valve to energize and shift to the cooling position. To ensure
that the 3-way diverting valve is energized and in the “cooling” (forward)
position, observe the position of the 3-way diverting valve actuator shaft
pinch bolt in the following gure; if properly shifted, the pinch bolt will be in
the forward position.
1
2
COOLING
(FORWARD)
EVACUATE
(CENTER)
DEHUMIDIFICATION
(REARWARD)
1. PUSH RED TAB IN DIRECTION INDICATED.
2. PUSH ACTUATOR SHAFT DOWN TOWARD THE
CENTER-OF-TRAV EL POSITION
Figure 19. Setting 3-Way Diverting Valve to Evacuate Position
5. The charge must be checked with the system in cooling operation
(dehumidication OFF). After testing and charging as required, set the
thermostattoforceademandfordehumidication.
2.5. Insulating and Sealing the Unit
IMPORTANT
Allpiping,meteringdevices,andconnectionsmustbeinsulatedtopreventmois-
turedamagecausedbysweating.
Sealthe unitso thatwarm airis not allowed into thecabinet.This isespecially
importantwhentheunitisinstalledinanunconditionedarea.Makesuretheliquid
lineentrypointsaresealedwitheitherrefrigeranttubeinsulatingmaterialorwith
Permagum.
2.6. Other System Components
2.6.1. Blower Control
When Humiditrol units are to be applied with an indoor unit that has a variable
speedmotor(VSM),thenrefertotheindoorunitinstallationinstructionforsetting
blowerspeed.
2.6.2. Thermostat and Sensor
RefertotheComfortSense7500,iComfortE30,M30orS30ThermostatInstallation
andSetupGuidefornon-communicatinginstallation,wiring,andsetup.
NOTE: Lennox communicating outdoor units have an outdoor sensor installed.
If these units are connected to a Lennox communicating thermostat, an
optional outdoor sensor is not needed.
IMPORTANT
EitheraCS7500oriComfortfamilythermostatalongwithaproperlyconnected
outdoortemperaturesensorarerequiredfortheHumiditrolunittofunctionprop-
erly.
Installtheremotesensorontheoutsideofanorthernwallofthehome,awayfrom
directsunlightorotherheatsourcesthatmayaffectitsabilitytoaccuratelysense
outdoortemperature.
2.7. Using Humiditrol Comfort Adjust
IfHumiditrolisenabledintheinstallersettings,thentheHumiditrolAdjustmentin
theUserSettingsaffectsovercoolingoperation(see“Table6.HumiditrolComfort
Adjust Parameters” on page 20 and “Figure 20. Thermostat Operation with
HumiditrolEnabled”onpage20describetheparametersandillustrateHumiditrol
operationundertypicalsettings).

Related product manuals