3
1.2. Additional Parts Required
Separately-ordered components are restricted to those listed in the Product
Specicationsandthepricebook
Table 2. Additional Parts
Quantity Description
Application
specic
OutdoorTemperatureSensor(X2658)
75VA24VACindoorunittransformer(12P61)isrequiredwhentheHumiditrolunitis
installedwithatwo-stageheatpumpsystem.
HumiditrolInsulationandPipingKit(referto“Figure1.DecisionTree”onpage
5).
HumiditrolZoningAccessory(39W67).Requiredwheninstallinginsystemwith
HarmonyIIIzoningsystem.
HumiditroliscompatiblewiththefollowingLennoxthermostats:
Table 3. Compatible Lennox Thermostats
Description
ComfortSense
®
7500thermostat(13H14)
iComfort
®
E30SmartThermostat(15S64)
iComfort
®
M30Thermostat(15Z69)
iComfort
®
S30UltraSmartThermostat(12U67)
IMPORTANT
TheapprovedapplicationfortheHumiditrolunitisrestrictedtothoselistedinthe
ProductSpecicationsandpricebook
NOTE: Due to Lennox’ ongoing commitment to quality, features and options are
subject to change without notice and without incurring liability. Improper
installation, adjustment, alteration, service or maintenance can cause
property damage or personal injury. Installation and service must be
performed by a qualied installer and servicing agency.
1.3. Introduction
Humiditrol
®
is designed for installation with a Lennox HFC-410A split-system
outdoor unit and an air handler or a furnace with a variable speed blower. It is
designedforindoorinstallationsonlyineitherup-oworhorizontalairdischarge
applications.
NOTE: Humiditrol is not compatible with variable-capacity outdoor units!
• HumiditrolisforuseonlyonHFC-410Asystemswiththermalexpansionvalve
installed.
• Prior to installation, study the decision tree (see “Figure 1. Decision Tree” on
page 5) to conrm that all application requirements for Humiditrol installation
aremet.
• Lowambientpressureswitchtypecontroloptioncanbeappliedtothistypeof
system down to 30ºF. For low ambient kit part numbers, refer to the Product
Specicationsaccessoriessection.
NOTE: The low ambient control option (down to 0ºF) is not compatible with
Humiditrol.
Beforebeginninginstallation,besuretheHVACsystemcomponentsarecompatible
with the Humiditrol. See “Figure 1. Decision Tree” on page 5 for the system
decision tree that describes compatible components of the system. One of the
followingthermostatsisrequiredfortheHumiditrolsystem:
1.3.1. ComfortSense
®
7500 Thermostat
NOTE: When wiring the thermostat into the system, be sure these requirements
are met:
• Minimum18gaugethermostatwireisused.
• Maximumthermostatwirerunlengthdoesnotexceed300feet(90m).
• Totalloadfromanythermostatconnectionislessthan1amp.
1.3.2. iComfort
®
Family of Thermostats
NOTE: When wiring the thermostat into the system, be sure these requirements
are met:
• Minimum18gaugethermostatwireisused.
• Maximumthermostatwirerunlengthdoesnotexceed1500feet(455m)
• Totalloadfromanythermostatconnectionislessthan1amp.
1.3.3. Operation Overview
NOTE: These instructions are intended as a general guide and do not supersede
local codes in any way. Consult authorities having jurisdiction before
installation.
• The Humiditrol unit operates to dehumidify, as required, when ambient
temperaturesarebelow95ºF.
• However,whentemperaturesreach95ºF,coolinganddehumidicationdemands
are both serviced by increased cooling system run-time and does not use
Humiditrol.
• Neither the CS7500 or any of the iComfort family of thermostats will activate
Humiditrolwhentheambienttemperatureisatorabove95ºF.
• Priortosystemcheckout,considertheoutdoorambienttemperaturesincethe
Humiditrolwillnotoperateabove95ºF.
• Plantestingtobeconductedwhentemperaturesarebetween65ºFand95ºFto
ensureproperHumiditrolsetupandcheckoutoperation.
• Humiditrolremovesmoisturefromtheindoorairatagreaterratethancooling
alone. On a call for dehumidication, the indoor blower is slowed down, the
outdoorfan isoperated ata lower speed,and thecompressor isupstaged to
high-stageoperation(two-stageunits).Theindoorcoolingcoilnowoperatesasa