EasyManua.ls Logo

Lennox EDA - Operation Notes; Wiring Diagram Locater

Lennox EDA
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
lowertemperatureremovingadditionalhumidity.Atthesametime,theHumiditrol
three-wayvalvesrepositionthemselvesandtheHumiditrolcoilbecomesactive.
Thisallowscondenserheattowarmtheindoorairtoavoidexcessiveovercooling
ofthehome.Duringcoolingonly(noHumiditroloperation)theHumiditrolcoilis
inactive.
TheHumiditrolcoilisaddedtoanHVACsystemdownstreamoftheindoorcoil.
Indehumidicationmode,thecoilbecomesanextensionoftheoutdoorcoiland
injectsheatintotheindoorairstream.
Thisdehumidicationmodeallowssignicantlyimprovedcontrolofthehumidity
intheconditionedspacewithlesschanceofovercoolingthespace.
The assembly includes a set of 3-way diverting valves which will either route
refrigerantthroughtheHumiditrolcoil,orcausetherefrigeranttobypassthethat
coil,dependingonthemodeofoperation.
1.3.4. Operation Notes
Dehumidicationwillnotoccurwhentheoutdoortemperatureisatorabove95ºF
orindoortemperatureisatorbelow65ºF.
Whenoperatingincooling(orheatpumpheating)mode,alltemperaturesand
pressureswillbeasinanormalsystem.
WhenthethermostatisinHumiditrolmode,andafteracoolingdemandhasbeen
satisedbutadehumidicationdemandpersists,andtheroomtemperatureis
within the MIN, MID, MAX parameters described in Using Humiditrol Comfort
Adjust(see“2.7.UsingHumiditrolComfortAdjust”onpage19),theairhandlers
willoperateatreducedairowwiththecompressorathighspeed.
When the unit is in the dehumidication mode, the thermostat will display
“dehumidifyoranicon”onthehomescreen.
IMPORTANT
TheCleanAirActof1990banstheintentionalventingofallrefrigerants(CFC,
HFC,andHCFC)asofJuly1,1992.Approvedmethodsofrecovery,recycling
or reclaiming must be followed. Fines and/or incarceration may be levied for
non-compliance
WARNING
Improperinstallation,adjustment,alteration,serviceormaintenancecancause
propertydamage,personalinjuryorlossoflife.
Installation and service must be performed by a licensed professional HVAC
installer(orequivalent)oraserviceagency.
WARNING
Riskofexplosionorre.
Cancauseinjuryordeath.
Recoverallrefrigeranttorelievepressurebeforeopeningthesystem.
1.4. Wiring Diagram Locater
Table 4. Wiring Diagram Locater
Thermostat Indoor Unit Control Outdoor Unit Control Wiring Diagram
ComfortSense 7500 or
iComfort M30
Non-communicating Non-communicating
“Figure11.CS7500
orM30withanyNon-
CommunicatingIndoor
andOutdoorUnits”on
page12.
ComfortSense 7500 or
iComfort M30
Non-communicating
Lennox
Communicating
wiredas24VAC
Conventional
“Figure12.CS7500
orM30withNon-
CommunicatingIndoor
andCommunicating
OutdoorUnits
WiredforNon-
Communicating”on
page13.
ComfortSense 7500 or
iComfort M30
Lennox
Communicatingwired
asnon-communicating
Lennox
Communicatingwired
asnon-communicating
“Figure13.CS7500
orM30with
CommunicatingIndoor
andOutdoorUnits
withBothWiredNon-
Communicating”on
page14.
iComfort E30
Lennox
Communicatingwired
asnon-communicating
Lennox
Communicatingwired
asnon-communicating
“Figure14.E30
withbothIndoor
andOutdoor
Communicating
UnitsWiredforNon-
Communicating”on
page15.
iComfort S30
Lennox
Communicating
Lennox
Communicating
“Figure15.S30
WiredSystemfor
Communicating”on
page16.

Related product manuals