Energence
®
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 27
HUMIDITROL
®
DEHUMIDIFICATION SYSTEM RATINGS
45.7 kW - LGH156H4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
1965 21.1 4.13 0.58 0.77 0.97 17.7 4.65 0.51 0.77 1.00 14.3 5.20 0.47 0.75 1.00 10.9 5.74 0.40 0.75 1.00
2455 23.0 4.16 0.60 0.85 1.00 19.3 4.67 0.55 0.83 1.00 15.4 5.20 0.49 0.83 1.00 11.7 5.72 0.43 0.81 1.00
2945 25.3 4.18 0.63 0.91 1.00 21.0 4.69 0.57 0.89 1.00 16.7 5.20 0.51 0.86 1.00 12.5 5.72 0.46 0.86 1.00
1965 24.0 4.21 0.41 0.59 0.77 20.6 4.75 0.34 0.55 0.78 17.3 5.28 0.27 0.50 0.77 14.0 5.81 0.18 0.48 0.77
2945 26.1 4.21 0.42 0.64 0.85 22.3 4.75 0.35 0.59 0.85 18.5 5.28 0.27 0.56 0.86 14.8 5.81 0.19 0.52 0.86
2945 28.1 4.22 0.44 0.67 0.91 23.9 4.75 0.36 0.63 0.93 19.7 5.28 0.27 0.60 0.93 15.7 5.80 0.18 0.56 0.93
1965 26.8 4.29 0.25 0.42 0.57 23.6 4.83 0.16 0.34 0.53 20.4 5.36 0.07 0.28 0.48 17.2 5.92 -0.03 0.21 0.45
2455 28.9 4.28 0.26 0.42 0.61 25.3 4.81 0.15 0.36 0.57 21.6 5.37 0.05 0.30 0.55 17.9 5.89 -0.06 0.23 0.51
2945 31.0 4.27 0.26 0.45 0.64 26.9 4.81 0.14 0.38 0.62 22.9 5.34 0.03 0.32 0.60 18.9 5.89 -0.09 0.24 0.58
45.7 kW - LGH156H4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
1965 35.0 6.30 0.66 0.85 1.00 31.0 7.15 0.64 0.87 1.00 27.1 8.02 0.63 0.89 1.00 23.1 8.87 0.59 0.89 1.00
2455 38.0 6.32 0.70 0.92 1.00 33.5 7.19 0.70 0.94 1.00 29.1 8.04 0.68 0.95 1.00 24.7 8.91 0.66 0.95 1.00
2945 41.0 6.35 0.75 0.96 1.00 36.1 7.22 0.75 0.99 1.00 31.3 8.08 0.75 1.00 1.00 26.4 8.94 0.76 1.00 1.00
1965 39.7 6.39 0.48 0.66 0.82 35.5 7.24 0.46 0.65 0.85 31.3 8.10 0.42 0.64 0.87 27.1 8.96 0.38 0.64 0.88
2945 42.8 6.44 0.51 0.70 0.90 38.1 7.28 0.48 0.70 0.92 33.4 8.14 0.45 0.70 0.93 28.6 8.99 0.42 0.68 0.96
2945 45.8 6.47 0.53 0.75 0.96 40.6 7.32 0.51 0.75 0.97 35.3 8.18 0.49 0.74 0.97 30.2 9.03 0.46 0.74 1.00
1965 44.2 6.49 0.31 0.47 0.61 39.8 7.36 0.27 0.43 0.60 35.5 8.20 0.23 0.40 0.60 31.2 9.04 0.17 0.37 0.59
2455 47.6 6.53 0.31 0.49 0.66 42.6 7.40 0.28 0.46 0.65 37.7 8.24 0.23 0.43 0.65 32.6 9.09 0.17 0.40 0.65
2945 50.9 6.59 0.33 0.51 0.70 45.3 7.44 0.28 0.49 0.71 39.7 8.29 0.23 0.46 0.71 34.3 9.12 0.17 0.44 0.72
52.8 kW - LGH180H4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
2265 24.5 4.75 0.58 0.77 0.95 21.1 5.34 0.52 0.77 0.97 17.6 5.90 0.47 0.74 0.98 14.1 6.49 0.43 0.74 1.00
2830 26.0 4.78 0.62 0.85 1.00 22.0 5.33 0.58 0.86 1.00 18.0 5.89 0.56 0.86 1.00 14.1 6.45 0.52 0.86 1.00
3400 27.5 4.82 0.65 0.92 1.00 23.0 5.34 0.64 0.93 1.00 18.6 5.88 0.62 0.99 1.00 14.2 6.41 0.60 1.00 1.00
2265 27.8 4.84 0.42 0.59 0.76 24.2 5.44 0.35 0.55 0.75 20.6 6.01 0.28 0.51 0.75 16.9 6.58 0.21 0.48 0.75
3400 29.0 4.89 0.44 0.64 0.83 25.0 5.45 0.38 0.62 0.85 21.2 5.98 0.32 0.59 0.87 17.2 6.53 0.26 0.56 0.88
3400 30.2 4.91 0.46 0.68 0.91 25.9 5.44 0.41 0.67 0.95 21.7 5.97 0.34 0.66 0.96 17.5 6.50 0.29 0.66 0.99
2265 31.1 4.96 0.25 0.40 0.55 27.3 5.52 0.17 0.34 0.52 23.5 6.11 0.09 0.29 0.47 19.8 6.69 0.01 0.23 0.45
2830 32.0 4.97 0.25 0.42 0.59 28.1 5.53 0.17 0.37 0.57 24.2 6.09 0.08 0.32 0.54 20.5 6.65 0.00 0.26 0.53
3400 32.9 5.00 0.25 0.45 0.64 28.9 5.55 0.17 0.40 0.63 25.0 6.06 0.08 0.35 0.61 21.1 6.60 -0.01 0.29 0.60
52.8 kW - LGH180H4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
2265 41.3 7.16 0.67 0.84 1.00 37.0 8.05 0.66 0.85 1.00 32.7 8.95 0.65 0.86 1.00 28.3 9.84 0.63 0.88 1.00
2830 43.5 7.20 0.72 0.92 1.00 38.6 8.08 0.72 0.94 1.00 33.6 8.95 0.72 0.95 1.00 28.8 9.84 0.72 0.95 1.00
3400 45.9 7.24 0.77 0.98 1.00 40.4 8.12 0.78 1.00 1.00 35.0 9.00 0.79 1.00 1.00 29.4 9.87 0.80 1.00 1.00
2265 45.8 7.29 0.50 0.64 0.80 41.5 8.19 0.46 0.64 0.83 37.1 9.08 0.43 0.64 0.84 32.6 9.98 0.40 0.63 0.86
3400 48.1 7.33 0.51 0.69 0.85 43.1 8.21 0.50 0.68 0.89 38.2 9.10 0.48 0.70 0.91 33.2 9.97 0.46 0.70 0.95
3400 50.3 7.36 0.56 0.70 0.86 44.8 8.23 0.53 0.72 0.92 39.2 9.09 0.51 0.75 0.95 33.7 9.95 0.49 0.77 1.00
2265 50.4 7.44 0.32 0.47 0.62 45.9 8.33 0.28 0.44 0.60 41.4 9.21 0.23 0.41 0.60 37.1 10.10 0.18 0.38 0.59
2830 52.5 7.46 0.32 0.45 0.56 47.8 8.35 0.28 0.43 0.60 42.7 9.22 0.23 0.44 0.64 37.9 10.09 0.20 0.43 0.67
3400 54.9 7.49 0.33 0.42 0.52 49.5 8.36 0.28 0.44 0.60 43.9 9.23 0.24 0.46 0.69 38.6 10.09 0.19 0.47 0.77