Energence
®
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 29
HUMIDITROL
®
DEHUMIDIFICATION SYSTEM RATINGS
88 kW - LGH300S4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

3775 26.9 6.38 0.56 0.77 0.97 22.4 7.00 0.48 0.74 1.00 17.8 7.63 0.39 0.71 1.00 13.3 8.26 0.30 0.68 1.00
4485 28.5 6.45 0.60 0.80 0.99 23.9 7.06 0.52 0.79 1.00 19.3 7.66 0.43 0.77 1.00 14.8 8.28 0.35 0.76 1.00
5195 30.0 6.52 0.63 0.85 1.00 25.4 7.11 0.55 0.84 1.00 20.9 7.70 0.47 0.82 1.00 16.2 8.29 0.40 0.82 1.00

3775 31.1 6.52 0.38 0.56 0.74 26.6 7.16 0.28 0.49 0.73 21.8 7.80 0.17 0.44 0.72 17.1 8.45 0.07 0.38 0.71
4485 32.8 6.57 0.40 0.58 0.77 27.9 7.20 0.30 0.52 0.77 22.9 7.84 0.19 0.48 0.78 17.9 8.47 0.08 0.44 0.79
5195 34.6 6.62 0.41 0.60 0.81 29.3 7.25 0.31 0.56 0.82 24.0 7.87 0.20 0.52 0.83 18.7 8.49 0.09 0.48 0.85

3775 35.4 6.65 0.19 0.35 0.51 30.5 7.32 0.07 0.25 0.46 25.7 7.99 -0.04 0.17 0.40 21.0 8.65 -0.16 0.09 0.35
4485 37.2 6.69 0.19 0.35 0.53 31.9 7.35 0.07 0.27 0.48 26.6 8.01 -0.05 0.19 0.44 21.2 8.67 -0.17 0.11 0.40
5195 39.1 6.74 0.19 0.36 0.55 33.2 7.38 0.07 0.29 0.51 27.3 8.04 -0.07 0.21 0.49 21.4 8.70 -0.19 0.13 0.46
88 kW - LGH300S4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C

3775 68.3 12.69 0.68 0.86 1.00 62.0 14.12 0.67 0.88 1.00 55.6 15.55 0.67 0.90 1.00 49.3 16.96 0.66 0.91 1.00
4485 69.8 12.76 0.72 0.91 1.00 63.1 14.19 0.73 0.93 1.00 56.4 15.62 0.73 0.95 1.00 49.8 17.04 0.74 0.97 1.00
5195 71.5 12.84 0.76 0.95 1.00 64.3 14.26 0.78 0.97 1.00 57.3 15.71 0.79 0.98 1.00 50.3 17.13 0.82 0.99 1.00

3775 72.5 12.91 0.49 0.67 0.85 67.0 14.38 0.49 0.67 0.86 61.3 15.86 0.47 0.67 0.87 55.6 17.31 0.44 0.66 0.89
4485 73.3 13.04 0.52 0.70 0.89 67.5 14.48 0.51 0.71 0.91 61.8 15.93 0.50 0.72 0.94 56.0 17.37 0.49 0.72 0.96
5195 74.0 13.17 0.54 0.73 0.92 68.1 14.59 0.54 0.75 0.96 62.2 16.01 0.54 0.78 0.98 56.4 17.43 0.52 0.79 0.99

3775 76.8 13.12 0.33 0.48 0.63 71.9 14.63 0.29 0.47 0.63 67.2 16.17 0.26 0.44 0.62 62.2 17.70 0.23 0.41 0.62
4485 76.9 13.31 0.34 0.50 0.67 72.0 14.78 0.30 0.49 0.67 67.3 16.24 0.26 0.47 0.68 62.5 17.72 0.23 0.47 0.69
5195 76.8 13.50 0.34 0.52 0.70 72.1 14.92 0.31 0.52 0.72 67.5 16.33 0.27 0.51 0.75 62.9 17.74 0.24 0.50 0.77