IOM / ROOF-TOP FLEXY™ Series - Page 17
Check the setpoints on CLIMATIC™ (LF 20).
COMMISSIONING
C0
Password technician Level 63
C98
Type of Unit Refer to configuration table LF20
C99
Type of Unit [off] Flexy [on] Linea On or OFF
C103
Humidity and enthalpy management Option
[off] LINEA
[on] only Flexy with Advanced Pack
C77
(Linea) Authorisation of defrost. Threshold of temperature
of refrigerant fluid ( in°C)
1.0°C for R407c
-3.0°C for R22
C79
Defrost cycle end value indicating the nr of Start-ups of the
condenser fan to signify the end of defrost
Linea set to1
Flexy set to 3
C101
Activation of all seasons control option [ON] / [OFF] if fitted
C73
All seasons control option on FLEXY -
Otherwise – unloading 50% of the compressors in cooling
mode
Set to 20.0°C for Linea
Set to 12°C for Flexy
C74
If option all seasons control – shut down condenser fans -
Otherwise - 100% unloading of compressors in cooling
mode -
Set to 12.0°C for Linea
Set to 5.0°C for Flexy
C49
Threshold of activation of the power exhaust fan according
to the position of the economiser damper (in %)
Set to 50%
C46
Number of minutes of anticipation per degrees. This allows
an anticipated start-up in the morning mode depending on
the outside temperature.
Set to 0
C83
Maximum usable power for electric heat (in %)
C90
Choice of operating mode for KP17 [ON] = KP17 in ON / OFF mode
C91
Identification number for the J-Bus connections
C93
Identification number for the connections link between
boards
C94
Number of boards linked on the bus
C95
Selection of the operating mode for KP017
C96
Selection of exchange mode for room temperature and
humidity-
C97
Selection of exchange mode for outdoor temperature and
humidity
C100
Activation of the dual-speed option for fan supply (Flexy)
C101
Activation of the all seasons control option
C102
Activation of the optimised defrost option
C05
Fault reset Set to ON
C06
Remote control, On / Off Unit Set to ON ( the unit should start)