EasyManua.ls Logo

Lennox FCA 60

Lennox FCA 60
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 52 - IOM / ROOF-TOP FLEXY™ Series
GAS BURNERS
DIAGNOSTIC TABLE GAS BURNER
STAGES
NORMAL
OPERATION
FAULT ACTIONS SOLUTIONS
Heating
requested
Contactors
KM21-22
engaged
Contactors do
not engage
Check safety thermostats B29-
30 in the air duct before the gas
heat exchanger
Replace component
Contactors
KM21-22 are
engaged
Extraction fans
are running
Nothing
happens
Check the free movement of the
fan wheel
Check the supply temperature
limitation thermostats B45-46
Check GAS low pressure
switches B17-18
Check electrical connection on
the Honeywell control block
and on EF45-46 connection
boards
Check the fan supply voltage
Replace thermostat
Open GAS Supply
Replace EF 45-46 if
necessary
Extraction fan
ON
After 30
seconds: the
fire-up
electrode must
create sparks
Continuous
ventilation
without sparks
by electrode
Check position of the fire-up
electrode (refer to preliminary
checks and verifications §1)
Check the pressure drop at the
pressure switch : It must be
higher than 200 Pa
Check the good operation of the
pressure switch using an
Ohmmeter and by sucking
through the tube to create a
depression.
Check the operation the Backfire
thermostat B32-B33
Re-position the
pressure taping
tube.(§5.d)
Change the pressure
switch
Reset or replace the
Thermostat
Continuous
ventilation with
sparks created
by electrode
After 2 seconds
the gas burner
fires-up
After 4 second
the GAS Burner
still not running
and Safety
shutdown by
the Honeywell
Block.
Check injection pressure during
start-up (value for high heat)
Check the supply voltage to the
control box (continuous voltage).
Refer to figure 61.
Remove the control box from the
gas block. Check using an
ohmmeter the solenoid coil of
the GAS block (4 kOhm). Refer
to figure 62
Remove the air from the
pipe-work
Adjust the injection
pressure to high heat
value
Change the control box
if the GAS valve is OK.
Change the gas valve
control