Page 62 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002)
1st Level
Mini. Factory Maxi.
C 000
[Kp02] Password, technician level 0 # 255
C 001
[Kp17] [Mode] Required room temperature (in °c).
This value corresponds to the middle of the dead zone - (active for
Day mode only)
C 051 21.0°C C 050
C 002
[Kp17] Forced occupied mode (Day) –
This action deactivates automatically when the clock first pass
midnight - Yellow led lit
Off Off On
C 003
[Kp17] Cancels the override of day or night modes- Yellow led
flashing
Off Off On
C 004
[Kp17] Forced unoccupied mode (Night)
This action automatically deactivates when the clock pass midnight
for the second time –
Yellow led off
Off Off On
C 005
[Reset] Fault reset
Off Off On
C 006
[On / Off] Remote control, On / Off unit
Off Off On
C 007
[Kp02] Selection of the memory number for the defaults to be
visualized
1 # 5
C 008
[Kp02] [Mode] Mode selection for the visualization and the adjustment
of the settings
0 = Day, 1 = Week-End,
2 = Night, 3 = not used,
4 = Morning, 5 = Midday,
6 = Evening 7 = BMS
0 # 7
C 009
[Mode] Day of the week, Start of mode - (active for the Week-End
mode)
1 # 7
C 010
[Mode] Hour, Start of mode - (active for the modes Week-End, Night,
Morning, Midday, Evening)
0 h # h 22 h
C 011
[Mode] Minute, Start of mode - (active for the modes Week-end,
Night, Morning, Midday, Evening)
0 m # m 59 m
C 012
[Mode] Day of the week, End of mode - (active for the Week-End
mode)
1 # 7
C 013
[Mode] Hour, End of mode - (active for the modes Week-End,
Morning, Midday, Evening)
0 h # h 23 h
C 014
[Mode] Minute, End of mode - (active for the modes Week-End,
Morning, Midday, Evening)
0 m # m 59 m
C 015
[Mode] Required maximum room temperature (in °c) - Cooling set
point
8.0 c # c 35.0 c
C 016
[Mode] Required minimum room temperature (in °c) - Heating set
point
8.0 c # c 35.0 c
C 017
[Mode] Selection of humidity control mode
[Off] The relative humidity set points are taken into account (in %)
[On] The absolute humidity set points are taken into account - (in
g/kg)
Off Off On
C 018
[Mode] Required maximum room relative humidity (in %) –
Dehumidification set point
0 % # % 100 %
C 019
[Mode] Required maximum room absolute humidity (in g/kg)
Dehumidification set point
0.0 g/kg # g/kg 30.0 g/kg
C 020
[Mode] Required minimum room relative humidity (in %)
Humidification set point
0 % # % 100 %