USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002) - cont'd
1st Level
Mini. Factory Maxi.
C 021
[Mode] Required minimum room absolute humidity (in g/kg)
Humidification set point
0.0 g/kg # g/kg 30.0 g/kg
C 022
[Mode] Required minimum percentage for fresh air
0 % # % 100 %
C 023
[Mode] Stopping and running of the fan blower supply
[Off] The blower is stopped
[On] The blower is running.
Off # On
C 024
[Mode] Stopping and running of the fan blower supply in the
regulation dead zone
[Off] The blower is stopped
[On] The blower is running
Off # On
C 025
[Mode] Management of the low speed on the fan supply in the cooling
regulation zone
[Off] The fan is on high speed
[On] The fan is on low speed
Off # On
C 026
[Mode] Management of the low speed on the fan supply in the
regulation dead zone
[Off] The fan is on high speed
[On] The fan is on low speed
Off # On
C 027
[Mode] Management of the low speed on the fan supply in the
heating regulation zone
[Off] The fan is on high speed
[On] The fan is on low speed
Off # On
C 028
[Mode] Force the noise reduction mode
[On] 50% of the compressors are unloaded
Off # On
C 029
[Mode] Force the operation mode
Off # On
C 030
[Command] Force the low speed on fan blower supply
Off Off On
C 031
[Command] Force the fresh air damper in the closed position - (0%
fresh air)
Off Off On
C 032
[Command] Force the fresh air damper to its defined minimum set
point position.
Off Off On
C 033
[Command] Force fresh air damper in the fully open position - (100%
fresh air)
Off Off On
C 034
[Command] Force an unloading of the compressors
Off Off On
C 035
[Command] Force an unloading of the electric heat
Off Off On
C 036
[Command] Forced unloading of :
(FLEXY™) - 50% of the compressors - 100% of electrical heat
Off Off On
C 037
[Command] Force an unloading of all refrigeration parts
Off Off On
C 038
[Command] Force an unloading of all heating parts
Off Off On
C 039
[Safety limits] Room temperature low limit (in °c) - Threshold of
activation of the safety cut-out
5.0 c 10.0 c 20.0 c
C 040
[Safety limits] Room temperature high limit (in °c) - Threshold of
activation of the safety cut-out
20.0 c 40.0 c 40.0 c