IOM / ROOF-TOP FLEXY™ Series - Page 67
USING THE KP02 MAINTENANCE CONTROL DISPLAY
LIST OF SETPOINTS (LF 20 - APRIL 2002) - cont'd
2nd Level
Mini. Factory Maxi.
C 095
[Configuration] [Link] Selection of the operating mode –
[0] Inactive
[1] One kp17 for several units - All information on the kp17 connected
to the master unit is communicated to the slave units
[2] One unit in standby mode - The unit with the highest address
connected to the bus is stopped. If a fault is detected on another
unit, the faulty unit is stopped and the standby unit is started
automatically
[3] Same as choice 2 but the standby unit is changed every Tuesday
at 8 o’clock
0 # 3
C 096
[Configuration] [Link] Selection of exchange mode for room
temperature and humidity
[0] Inactive
[1] The room temperature and humidity of the master unit are
communicated to the slave units
[2] The room temperature and humidity are taken as the average of
the active probes.
0 # 2
C 097
[Configuration] [Link] Selection of exchange mode for outdoor
temperature and humidity
[0] Inactive
[1] The outdoor temperature and humidity of the master unit are
communicated to the slave units
[2] The outdoor temperature and humidity are taken as the average
of the active probes.
0 # 2
C 098
[Configuration] Type of unit
0 # 65535
C 099
[Configuration] Type of unit [Off] FLEXY
Off # On
C 100
[Configuration] Activation of the dual-speed option for fan supply
Off # On
C 101
[Configuration] Activation of the all seasons control option
Off # On
C 102
[Configuration] Activation of the optimised defrost option
Off # On
C 103
[Configuration] Activation of the humidity and the enthalpy
management option
Off # On
C 104
[Various] Override all set points to factory settings
Off Off On
C 105
[Various] reserved Lennox
0 0 65535