Page 68 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
VARIABLE LIST (LF 20 - April 2002)
1st Level
V 000 [Defects] error codes
V 001 [Value] Temperature (in °c), Room, Reference value
V 002 [Value] Relative humidity (in %), Room, Reference value
V 003 [Value] Absolute humidity (in g/kg), Room, Reference value
V 004 [Value] Temperature (in °c), Outdoor, Reference value
V 005 [Value] Relative humidity (in %), Outdoor, Reference value
V 006 [Value] Absolute humidity (in g/kg), Outdoor, Reference value
V 007 [Input] Temperature (in °c), Supply
V 008 [Input] Temperature (in °c), Mixing
V 009 [Input] Temperature (in °c), Free
V 010 [Input] Temperature (in °c), Chilled water
V 011 [Input] Temperature (in °c), Compressor, n°1
V 012 [Input] Temperature (in °c), Compressor, n°2
V 013 [Input] Temperature (in °c), Compressor, n°3
V 014 [Input] Temperature (in °c), Compressor, n°4
V 015 [Input] Temperature (in °c), Condenser, n°1
V 016 [Input] Temperature (in °c), Condenser, n°2
V 017 [Input] Temperature (in °c), Condenser, n°3
V 018 [Input] Temperature (in °c), Condenser, n°4
V 019 [Input] Temperature (in °c), Water condenser, Output exchanger
V 020 [Input] Signal, Shift of the set point
V 021 [Input] Pressure (in pa), Air flow, Supply fan
V 022 [Input] Signal (in ppm), Air quality sensor, Co²
V 023 [Input] Pressure (in b), Compressor, n°1
V 024 [Input] Pressure (in b), Compressor, n°2
V 025 [Input] Pressure (in b), Compressor, n°3
V 026 [Input] Pressure (in b), Compressor, n°4
V 027 [Output] Supply fan
V 028 [Output] Supply fan, Command low speed
V 029 [Output] Extraction fan
V 030 [Output] Compressor, n°1
V 031 [Output] Compressor, n°2
V 032 [Output] Compressor, n°3
V 033 [Output] Compressor, n°4
V 034 [Output] Compressor, Cycle reversing valve, Heat pump, n°1
V 035 [Output] Compressor, Cycle reversing valve, Heat pump, n°2
V 036 [Output] Compressor, Cycle reversing valve, Heat pump, n°3
V 037 [Output] Compressor, Cycle reversing valve, Heat pump, n°4
V 038 [Output] Compressor, Hot gas injection valve
V 039 [Output] Condenser fan, Command low speed
V 040 [Output] Condenser fan, n°1
V 041 [Output] Condenser fan, n°2
V 042 [Output] Condenser fan, n°3
V 043 [Output] Condenser fan, n°4
V 044 [Output] Pump
V 045 [Output] Electrical heater, n°1, 1st level
V 046 [Output] Electrical heater, n°1, 2nd level
V 047 [Output] Electrical heater, n°2
V 048 [Output] Gas grade, n°1, 1st level
V 049 [Output] Gas grade, n°1, 2nd level
V 050 [Output] Gas grade, n°2