IOM / ROOF-TOP FLEXY™ Series - Page 69
V 051 [Output] Gas grade, Reset
V 052 [Output] Economiser, Proportional action (0-255)
V 053 [Output] Chilled water coil, Proportional action (0-255)
V 054 [Output] Hot water coil, Proportional action (0-255)
V 055 [Output] Electrical heater, Static relays, Proportional action (0-255)
V 056 [Output] Humidifier, Proportionnel action (0-255)
V 057 [Statute] supply fan
1 = ok 2 = option air flow
3 = option low speed 4 = option air flow + low speed
6 = activation of a defect 7 = activation of a defect filters
8 = ventilation nonready
V 058 [Statute] Economiser
0 = option any air recycled 1 = all fresh air
2 = option economiser 3 = option enthalpy
4 = option co² 5 = option enthalpy + co²
6 = function enthalpy activates 7 = remote command active
8 = ventilation no ready
V 059 [Statute] Chilled water coil
0 = not configured 1 = ok
8 = ventilation no ready
V 060 [Statute] Hot water coil
0 = not configured 1 = ok
8 = ventilation no ready
V 061 [Statute] Compressor, n°1
0 = not configured 1 = option cooling only
2 = option heat pump 3 = defrost in progress
5 = limit outside temperature or remote command active
6 = activation of a defect 7 = activation of a defect condenser
8 = ventilation no ready
V 062 [Statute] Compressor, n°2
0 = not configured 1 = option cooling only
2 = option heat pump 3 = defrost in progress
5 = limit outside temperature or remote command active
6 = activation of a defect 7 = activation of a defect condenser
8 = ventilation no ready
V 063 [Statute] Compressor, n°3
0 = not configured 1 = option cooling only
2 = option heat pump 3 = defrost in progress
5 = limit outside temperature or remote command active
6 = activation of a defect 7 = activation of a defect condenser
8 = ventilation no ready
V 064 [Statute] Compressor, n°4
0 = not configured 1 = option cooling only
2 = option heat pump 3 = defrost in progress
5 = limit outside temperature or remote command active
6 = activation of a defect 7 = activation of a defect condenser
8 = ventilation no ready
V 065 [Statute] Condenser
0 = not configured 1 = option air condenser
2 = option water condenser 6 = activation of a defect
8 = ventilation no ready
V 066 [Statute] Pump
0 = not configured 1 = ok
6 = activation of a defect 8 = ventilation no ready
V 067 [Statute] Electrical heater
0 = not configured 1, 2 or 3 = number of stages
4 = static relays
5 = limit outside temperature or remote command active
6 = activation of a defect 8 = ventilation no ready
USING THE KP02 MAINTENANCE CONTROL DISPLAY