Page 70 - IOM / ROOF-TOP FLEXY™ Series
V 068 [Statute] Gas grade
0 = not configured 1, 2 or 3 = number of stages
6 = activation of a defect 8 = ventilation no ready
V 069 [Statute] Humidifier
0 = not configured 1 = ok
6 = activation of a defect 8 = ventilation no ready
V 070 [Regulation] Real set point, Cooling, Room
V 071 [Regulation] Real set point, Heating, Room
V 072 [Regulation] Power-factor, Cooling, Room
V 073 [Regulation] Power-factor, Heating, Room
V 074 [Regulation] Real set point, Supply
V 075 [Regulation] Power-factor, Cooling, Supply
V 076 [Regulation] Power-factor, Heating, Supply
V 077 [Regulation] Real set point, Dehumidification, Room
V 078 [Regulation] Real set point, Humidification, Room
V 079 [Regulation] Power-factor, Dehumidification, Room
V 080 [Regulation] Power-factor, Humidification, Room
V 081 [Mode] Number of the active mode
V 082 [Function] Number of the unit in standby
V 083 [Defects] Memory, Code
V 084 [Defects] Memory, Hour
V 085 [Defects] Memory, Minute
V 086 [Defects] Memory, Day
V 087 [Defects] Memory, Month
V 088 [Information] Non-standard program
V 089 [Information] Number of version of the program
USING THE KP02 MAINTENANCE CONTROL DISPLAY
CONFIGURATION
This information is taken into account by the program after having switched off/on the CLIMATIC, and a second time for C091
and C093 setpoints.
Set point ‘Eeprom’
(KP02 C.083) Maximum percentage of power of electrical heater 1
(KP02 C.090) On = KP17 in ON/OFF mode 1
(KP02 C.091) J.Bus - Number of slave (KP06, KP07, CLIMALINK, CLIMALOOK) 2
(KP02 C.093) Link - Identification number 2
(KP02 C.094) Link - Number of connected cards 1
(KP02 C.095) Link - Functions 1
(KP02 C.096) Link - Room Temperature and Humidity 1
(KP02 C.097) Link - Outside Temperature and Humidity 1
(KP02 C.098) See tables below 1
(KP02 C.100) On = Option Bi-Speed of the blower 1
(KP02 C.101) On = Option Regulation all seasons 1
(KP02 C.102) On = Option optimised defrost 1
(KP02 C.103) On = Option Enthalpy and management of the humidity 1