EasyManuals Logo

Lennox GCWB95W-150 Installation Instructions

Lennox GCWB95W-150
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
59
240012994 Rev. B [08/31/2020]
• METRIC GAS METERS
Natural Gas
MBH =
127,116 x cu meters
Seconds
For example: Gas Meter measures 0.1 cubic Meters in 100
seconds
MBH =
127,116 x 0.1
= 127 MBH
100
Propane Gas (LP)
MBH =
383,482 x cu meters
Seconds
NATIONAL BOARD OF BOILER AND PRESSURE VESSEL
INSPECTORS - Group composed of boiler and pressure
vessel inspectors representing states, cities and provinces
enforcing pressure equipment laws and regulations.
• PRESSURE TEST - Operation performed to verify gas
tight integrity of gas piping following its installation or
modication.
• PURGE - To free gas conduit of air or gas, or mixture of gas
and air.
• PURGE TIME - Period of time intended to allow for
dissipation of any unburned gas or residual products of
combustion.
• QUALIFIED AGENCY - Any individual, rm, corporation, or
company engaged in and responsible for:
Installation, testing, or replacement of gas piping, or
connection, installation, testing, repair or servicing
of appliances and equipment.
Experienced in such work.
Familiar with all precautions required.
Complies with all requirements of authority having
jurisdiction.
SAFETY RELIEF VALVE - Valve designed to relieve
pressure in hot water supply system when pressure exceeds
pressure capability of equipment.
• SAFETY SHUTOFF DEVICE - Device that will shut o gas
supply to controlled burner in event source of ignition fails.
• SEDIMENT TRAP - Gas piping arrangement designed to
collect any liquid or solid contaminant before reaching gas
valve.
SERVICE -Supply, installation, or maintenance of goods
carried out by a Qualied Installer / Service Technician.
14 - GLOSSARY
TWO PIPE SYSTEM - Type of venting that allows for
exhaust ue and intake air piping to be separated from each
other. Fresh air may be drawn in at a dierent area from
where ue terminal is located.
• VENT - Passageway used to convey ue gases from
appliance vent connector to outdoors.
• VENTING SYSTEM - Continuous open passageway from
of appliance vent connector to outdoors for purpose of
removing ue or vent gases.

Table of Contents

Other manuals for Lennox GCWB95W-150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox GCWB95W-150 and is the answer not in the manual?

Lennox GCWB95W-150 Specifications

General IconGeneral
BrandLennox
ModelGCWB95W-150
CategoryBoiler
LanguageEnglish

Related product manuals