42
H/D or ACC terminals are congured correctly for
dehumidify control.
Cooling demand only: Y1 and Y2 come on
initiating the conventional cooling only demand.
Dehumidication demand only: D is de-energized
(G should also be energized) but with out Y1 or
Y2. D remains o until the demand is satised or
if a true cooling demand comes on (unit must be in
cooling mode).
Both cooling and dehumidication demands:
Y1 and Y2 are ON (G must be ON and D is also
0 volts) When cooling is satised , D is still 0 volts
and G must stay ON until dehumidication demand
is satised.
Table 11. Auxiliary Dehumidier Option
Option Description
Normal
• Activate: If RH measured is >= (RH set point +
Activate: IF RH measured is >= (RH set point +
2%), and AND unit is in Cool mode (O = ON),,
THEN D is inactive (open circuit), AND G is
ON.
• Deactivate: IF RH measured is <= (RH set point
- 2%), or unit isn’t in Cool mode(B = ON), THEN
D is active. G returns to the state determined
by the thermostat control, either ON, Auto, or
CIRC.
Humidication Control
This option is available if the humidier accessory
is present and enabled in the Advanced Settings
> System Setup.
Under Advanced Settings > Terminal Settings,
verify that the H/D or ACC terminals are congured
correctly for humidify control.
Humidication is provided only when both a
humidication accessory is installed and the
thermostat is in heat mode.
• Setpoint Range: 15 – 45% RH
• Relative Humidity Controlled to 2% of Setpoint
(1% resolution)
• “H/D” Terminal to Humidier (deactivated during
cooling)
• This behavior changes based on H/D terminal or
ACC terminal
Normal and Max
The following table describes the function of normal
and max humidication settings.