POWER EXHAUST FAN PERFORMANCE
Return Air System Static Pressure Air Volume Exhausted
in. w.g. cfm
0.00 8630
0.05 8210
0.10 7725
0.15 7110
0.20 6470
0.25
0.30 5060
0.35 4300
0.40 3510
0.45
0.50 1840
CEILING DIFFUSER AIR RESISTANCE - in. w.g.
Air
Volume
cfm
RTD11-185S RTD11-275S
FD11-185S FD11-275S
2 Ends Open
1 Side/2 Ends
Open
All Ends &
Sides Open
2 Ends Open
1 Side/2 Ends
Open
All Ends &
Sides Open
5000 .51 .44 - - - - - - - - - .27 - - -
5200 .56 .48 .42 - - - - - - - - - .30 - - -
5400 .61 .52 .45 - - - - - - - - - .33 - - -
5600 .66 .56 .48 - - - - - - - - - .36 - - -
5800 .71 .51 - - - - - - - - - - - -
6000 .76 .63 .55 .36 .31 .27 .42
6200 .80 .68 - - - - - - - - - .46 - - -
6400 .86 .72 .63 - - - - - - - - - .50 - - -
6500 - - - - - - - - - .42 .36 .31 - - - .34
6600 .77 .67 - - - - - - - - - .54 - - -
6800 .83 .72 - - - - - - - - - .58 - - -
7000 1.03 .87 .76 .41 .36 .62 .40
7200 .80 - - - - - - - - - .66 - - -
7400 1.15 .84 - - - - - - - - - .70 - - -
7500 - - - - - - - - - .51 .46 .41 - - - .45
7600 1.20 1.02 .88 - - - - - - - - - .74 - - -
8000 - - - - - - - - - .43 - - - .50
8500 - - - - - - - - - .58 .50 - - - .57
- - - - - - - - - .67 .58 - - - .66
- - - - - - - - - .75 .65 - - - .74
10,000 - - - - - - - - - 1.00 .84 .73 - - - .81
10,500 - - - - - - - - - 1.10 .80 - - -
11,000 - - - - - - - - - 1.21 1.01 .88 - - -
CEILING DIFFUSER AIR THROW DATA - ft.
Model
No.
Air Volume
cfm
1
Model
No.
Air Volume
cfm
1
RTD11-185S
Step-Down
FD11-185S
Flush
RTD11-275S
Step-Down
FD11-275S
Flush
156
180
5600 28 - 37
210
240
300
7200 33 - 38 26 - 35
5800 42 - 51 7400 35 - 40 28 - 37
6000 44 - 54 40 - 50 7600 36 - 41
6200 45 - 55 42 - 51 7800 38 - 43 40 - 50
6400 46 - 55 43 - 52 8000 42 - 51
6600 47 - 56 45 - 56 8200 41 - 46 43 - 52
1
Throw is the horizontal or vertical distance an airstream travels on leaving the outlet
open.
8400 44 - 54
8600 44 - 50 46 - 57
8800 47 - 55
BLOWER DATA