Page 13
ELECTRICAL DATA 5 TON
Model No. LGM060U4E / LGM060U4P
1
 Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor Rated Load Amps 14.6 7 
Outdoor Fan 
Motor 
Full Load Amps 2.8 1.4 1.1
Power Exhaust 
(1) 0.33 HP
Full Load Amps 2.4 1.3 1
   20
Indoor Blower 
Motor
Horsepower   
Full Load Amps 4.4 2.3 2.4
2
   Maximum 
Overcurrent 
Protection (MOCP)
Unit Only 40  
With (1) 0.33 HP
Power Exhaust
40 20 
3
   Minimum 
Circuit 
Ampacity (MCA)
Unit Only 26 13 11
With (1) 0.33 HP
Power Exhaust
28 14 12
1
 Extremes of operating range are plus and minus 10% of line voltage.
2
 HACR type breaker or fuse.
3
 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
ELECTRICAL DATA 6 TON
Model No. LGM074U4E / LGM074U4P
1
 Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor Rated Load Amps 16.9 8.3 6.8
Outdoor Fan 
Motor 
Full Load Amps 2.8 1.4 1.1
Power Exhaust 
(1) 0.33 HP
Full Load Amps 2.4 1.3 1
   20
Indoor Blower 
Motor
Horsepower   
Full Load Amps 4.4 2.3 2.4
2
   Maximum 
Overcurrent 
Protection (MOCP)
Unit Only  20 
With (1) 0.33 HP
Power Exhaust
 20 
3
   Minimum 
Circuit 
Ampacity (MCA)
Unit Only 29  12
With (1) 0.33 HP
Power Exhaust
31 16 13
1
 Extremes of operating range are plus and minus 10% of line voltage.
2
 HACR type breaker or fuse.
3
 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.