Page 25
 IMPORTANT
1-Make sure that unit is installed in accordance with 
the installation instructions and applicable codes.
      
factoryinstalled, for loose connections. Tighten as 
required.
3-Check to ensure that refrigerant lines do not rub 
against the cabinet or against other refrigerant lines.
4-Check voltage at disconnect switch. Voltage 
must be within range listed on nameplate. If not, 
consult power company and have voltage condition 
corrected before starting unit.
up.
B-Blower Access
1 -   Disconnect jack/plug connector to blower motor. 
Also disconnect jack/plug connector heating limit 
switches on gas units.
2 -   Remove screws on either side of blower assembly 
3 -   Pull base toward outside of unit.
C-Determining Unit CFM
IMPORTANT -  Multi-staged  supply  air  units  are  factory-
set to run the blower at full speed when there is a blower 
(G) demand without a heating or cooling demand. Refer 
to the eld-provided, design specied CFM for all modes 
of operation. Use the following procedure to adjust motor 
pulley to deliver the highest CFM called for in the design 
spec. See Inverter Start-Up section to set blower CFM for 
all modes once the motor pulley is set.
1 -   The following measurements must be made with 
a dry indoor coil. Run blower (G demand) without 
a cooling demand. Measure the indoor blower 
        
measurements are taken.
Note - Static pressure readings can vary if not taken 
where shown.
2 -   With all access panels in place, measure static 
pressure external to unit (from supply to return). 
Blower performance data is based on static pressure 
3 -   Accessories. Use static pressure and RPM readings 
to determine unit CFM.
4 -   The blower RPM can be adjusted at the motor pulley. 
Loosen Allen screw and turn adjustable pulley 
clockwise to increase CFM. Turn counterclockwise 
        
minimum and maximum number of pulley turns as 
shown in table 5.
TABLE 5 
MINIMUM AND MAXIMUM PULLEY ADJUSTMENT
Belt Min Turns Open Max Turns Open
A Section No Min 5
B Section 1*
*No minimum number of turns open when B belt is used 
LOCATION OF STATIC PRESSURE READINGS
SUPPLY AIR
READING
LOCATION
SUPPLY
TURN
INSTALLATIONS WITH DUCTWORK
SUPPLY
TURN
INSTALLATIONS WITH CEILING DIFFUSERS
MAIN
DUCT RUN
FIRST BRANCH
OFF OF MAIN RUN
DIFFUSER
ROOFTOP UNIT
ROOFTOP UNIT
SUPPLY AIR
READING
LOCATION
RETURN AIR
READING LOCATION
RETURN AIR
READING
LOCATION
FIGURE 8