EasyManua.ls Logo

Lennox MCA Series - Timer off Operation; Modify Timer ON;OFF Settings; 7 Connection to Centralized Controller; Set Indoor Unit Address for Centralized Control (Used with VRF Only)

Lennox MCA Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
hours,thentheincrementbecomesonehour.
6.5.7. Timer OFF Operation
1. Pressthe Timer OFF button. The TimerOFF icon, the
lastauto-offtime,and“h”willdisplay.
2. PresstheTimer OFFbuttonagaintosettheamountof
timebeforetheindoorunitstopsoperation.Eachpress
will increase the time in half hour increments until 10
hours,thentheincrementbecomes1hour.
6.5.8. Modify Timer ON/OFF settings
1. Press either the Timer ON button or the Timer OFF
buttontomodifythatsetting.
2. Usetheuparrowanddownarrowbuttonstochangethe
timedoperationintervals.
3. Setthetimerto0.0toturnofftimedoperation.
7. Connection to Centralized Controller
7.1. Set Indoor Unit Address for Centralized
Control (Used with VRF Only)
All indoor units connected to a centralized controller must
haveauniqueaddress.UsetheS1dipswitchandtheS2
dialswitchtosettheaddressforeachindoorunit.Thetable
belowshowshowtosettheuniqueaddresses.
Allindoorunitsarefactorysetto“0”.Tochangetheaddress
to“1”,movethedialswitchtothe1position,donotadjust
thedipswitches.Tochangetheaddressto“35”,movedip
switch1totheUPpositionandmovethedialswitchtothe
3 position.
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
1
2
ON
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
1
2
ON
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
1
2
ON
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
1
2
ON
S1+S2
FOR SETTING ADDRESS
RANGE
ADDRESS
FACTORY SETTING
0 ~ F 0 ~ F 0 ~ F 0 ~ F
0 ~ 15 16 ~ 31 32 ~ 47 48 ~ 63
DIP SWITCH
HANDLES
LEFT - DOWN
RIGHT - DOWN
LEFT - DOWN
RIGHT - UP
LEFT - UP
RIGHT - DOWN
LEFT - UP
RIGHT - UP
Figure 13. Dip Switches
Indoor Unit Address is 0
BothdipswitchhandlesareDOWN,dialpointsto0.
Indoor Unit Address is 32
Dipswitch1isUPanddipswitch2isDOWN,dialpointsto0.
Switchlocationandcolorvariesforeachindoorunit.Twoexamplesareshownabove.
Figure 14. Dip Switch Settings

Table of Contents

Other manuals for Lennox MCA Series

Related product manuals