EasyManua.ls Logo

Lennox MCFA036S4-*P - Four-Way Valve Testing

Lennox MCFA036S4-*P
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
157
29.4. Four-Way Valve
a. Poweron,useadigitaltestertomeasurethevoltage,whentheunitoperatesincooling,itis0V.Whentheunitoperates
inheating,itisabout230VAC.Ifthevalueofthevoltageisnotintherange,thePCBmusthaveproblemsandneedsto
be replaced.
Figure 78. Measure Voltage
b. Turnoffthepower,useadigitaltestertomeasuretheresistance.Thevalueshouldbe1.8~2.5KΩ.
Figure 79. Measure Resistance

Table of Contents

Other manuals for Lennox MCFA036S4-*P

Related product manuals