EasyManua.ls Logo

Lennox MCFA036S4-*P

Lennox MCFA036S4-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
162
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
Figure 84. Heating Mode
Heating Mode
Plusalltheindoorcapacityrequesttogether,thenmultiplyitbyT4.
Whenthereisonlyoneindoorunit:
T1 Ts
4
0
a
3
1
-1
3
1
2
0
b
c
d
e
f
2
Capacity Area a b c d e f
Norm Code (N) 3 2 1.5 1 .5 0
Model 9K 12K 18K
HP 1.0 1.2 1.5
OutdoorTemperature(T4)
Heating
<0°C <12°C 12°Cto17°C ≥17°C
<32°F <53.6°F 53.6°Fto77°F ≥62.6°F
ModifyRate 120% 80% 40% 20%
Whentheremorethanoneindoorunit:
OutdoorTemperature(T4)
Heating
<0°C <12°C 12°Cto17°C ≥17°C
<32°F <53.6°F 53.6°Fto62.6°F ≥62.6°F
ModifyRate 120% 100% 80% 60%
NOTE: The nal result is integer.
ThenmodifyitaccordingtoT2average(correction):

Table of Contents

Other manuals for Lennox MCFA036S4-*P

Related product manuals