Figure 3. Backup Mode
2.2.3. Room Sensor Back-Up Mode Set Points
The following set points are available when primary mode is set to NETWORK THERMOSTAT and the backup sensor mode
is set to either RETURN AIR BACK or ROOM SENSOR. All available set points have a range of 40.0°F to 95.0°F. The listed
values below are defaults.
Occupied Heating set point: 70.0°F
Unoccupied Heating set point: 60.0°F
Occupied Cooling set point: 75.0°F
Unoccupied Cooling set point: 85.0°F
Use parameters 142 and 147 for stage differential and dead-band options to adjust set points in room sensor mode.