Page 12
2.2.8. Room Sensor Parameters
Any of the parameters listed in table 7, can be directly modified using the following method:
Go to SETTINGS > RTU OPTION > EDIT PARAMETER =
Table 7. Room Sensor Parameter Summary
Control Parameter Control Value
Unit Description
P Screen Name Short Description Min. Default Max.
Electric Heat
63 HT ELEC STG UP TMR
Electric Heat Maximum
Lower Stage Run Time in
Room Sensor
Applications
0 912 3600 Sec
Stage up timer. The maximum time that
lower stage runs before calling next
heat stage. Used in room sensor ap
plications.
Disabled if set to 0.
64 HT ELEC STG DWN TMR
Electric Heat Time Delay
for Lower Stage
Termination Following
Higher Stage Termination
0 0 3600 Sec
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
Gas Heat
74 HT GAS STG UP TMR Gas Stage Up Timer 0 912 3600 Sec
Stage-up timer. The maximum time that
lower stage runs before calling next
heat stage. Used in room sensor ap
plications.
Disabled if set to 0.
75 HT GAS STG DWN TMR Gas Stage Down Timer 0 0 3600 Sec
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
Cooling
101 CL STG 2 STGUP TIME
Maximum Stage 1
Cooling Time Before Call
for Stage 2 Cooling
0 912 3600 Sec
Stage 2 stage up timer. The maximum
time that cooling stage 1 runs before
calling cooling stage 2.
Used in room sensor applications.
Disabled if set to 0.
102 CL STG 3 STGUP TIME
Maximum Stage 2
Cooling Time Before Call
for Stage 3 Cooling
0 912 3600 Sec
Stage 3 stage up timer. The maximum
time that cooling stage 2 runs before
calling cooling stage 3.
Used in room sensor applications.
Disabled if set to 0.
103 CL STG 4 STGUP TIME
Maximum Stage 3
Cooling Time Before Call
for Stage 4 Cooling
0 912 3600 Sec
Stage 4 stage up timer. The maximum
time that cooling stage 3 runs before
calling cooling stage 4.
Used in room sensor applications.
Disabled if set to 0.
104 CL STAGE DOWN TIME
Cooling Stage Down
Time
0 912 3600 Sec
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
General
133 ZONE SENS STRTUP DLY
Room Sensor Start-up
Delay
2 2 30 Min
Delay on any power-up or reset. During
the delay, no blower, heating, or cooling
operation will occur.
May be used to stagger unit start-ups.
Does NOT delay demands in thermo
stat mode.
Zone Sensor Start-up Delay is termin
ated if message from Comfort Sensor
or NCP is received.