Table 64. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.Parameter Short DescriptionScreen Name
192 SRV OUTPT DB TEMP
Service Output Deadband for
Temperature
1.0 8.0 162.0 °F Service Output Deadband for Temperature
193 SRV OUTPT DELAY Service Output Delay 64 416 8160 Seconds Service Output Delay
194 LOAD SHED NUM COMP
Number of compressors to shed
during load shedding
0 0 15 Option
Number of compressors to be turned off when load shedding is act
ive.
196 MAC ADDRESS MAC Address 0 128 128 Address
BACnet MAC Address. A value of 0-127 sets the BACnet MAC ad
dress to that value.
197 BAUD RATE Baud Rate
9.6K
19.2K
38.4K
76.8K
Option Baud rate setting.
System 3 Parameters
201 DACC OAT RS ADJ BND
Discharge Air Control Cooling
Outdoor Air Temperature
Adjustment Band
0.0 0.0 30.0 °F
Discharge Air Control Cooling outdoor temperature ambient cool
ing adjustment reset band.
Also used to reset free cooling set point (Parameter 159).
202 DACC OAT RS ADJ SP
Discharge Air Control Cooling
Outdoor Air Temperature
Cooling Reset Set Point
40.0 80.0 100.0 °F
Discharge Air Control Cooling outdoor air temperature cooling re
set set point.
Also used to reset free cooling set point (Parameter 159).
203 DACC OAT RS PRP BND
Discharge Air Control Cooling
Outdoor Ambient Air
Temperature Cooling
Proportional Band
1.0 20.0 60.0 °F
Discharge Air Control Cooling outdoor ambient temperature cool
ing proportional band.
Also used to reset free cooling set point (Parameter 159).
204 DACC RAT RS ADJ BND
Discharge Air Control Cooling
Return Air Reset Adjustment
Band
0.0 0.0 30.0 °F
Discharge Air Control Cooling return air reset adjustment band.
0 disables return air cooling reset.
Also used to reset free cooling set point (Parameter 159).
205 DACC RAT RS ADJ SP
Discharge Air Control Return Air
Reset Adjustment Set Point
50.0 70.0 80.0 °F
Discharge Air Control Cooling return air reset set point.
Also used to reset free cooling set point (Parameter 159).
206 DACC RAT RS PRP BND
Discharge Air Control Cooling
Return Air Reset Proportional
Band
1.0 10.0 30.0 °F
Discharge Air Control Cooling return air reset proportional band.
Also used to reset free cooling set point (Parameter 159).
207 DACC RS LIMIT
Discharge Air Control Cooling
Reset Limit
5.0 10.0 20.0 °F
Discharge Air Control Cooling total reset limit. This limits the total
DACC reset allowed.
Also used to reset free cooling set point (Parameter 159).
208 DACH OAT RS ADJ BND
Discharge Air Control Heating
Outdoor Air Temperature
Resent Adjustment Band
0.0 0.0 30.0 °F
Discharge Air Control Heating outdoor temperature reset adjust
ment band.
209 DACH OAT RS ADJ SP
Discharge Air Control Heating
Reset Adjustment Set Point
-31.0 40.0 60.0 °F Discharge Air Control Heating outdoor temperature reset set point.