Table 7. Room Sensor Parameter Summary
Control Parameter
DescriptionUnit
Control Value
P DescriptionUnitMax.DefaultMin.Short DescriptionScreen Name
146 COOL STAGE3 DIFFER
Cooling Stage 3
Differential
0.00 1.50 3.00 °F
Cooling stage 3 differential. Used only
with room sensor applications.
Differential temperature must be great
er than or equal to Parameter 145 and
less than or equal to Parameter 147.
147 COOL STAGE4 DIFFER
Cooling Stage 4
Differential
0.00 2.00 3.00 °F
Cooling stage 4 differential. Used only
with room sensor applications.
Differential temperature must be great
er than or equal to Parameter 146.
148 HEAT STAGE1 DIFFER
Heating Stage 1
Differential
0.00 0.50 3.00 °F
Heating stage 1 differential. Used only
with room sensor applications.
Differential temperature must be less
than or equal to Parameter 149.
149 HEAT STAGE2 DIFFER
Heating Stage 2
Differential
0.00 1.00 3.00 °F
Heating stage 2 differential. Used only
with room sensor applications.
Differential temperature must be great
er or equal to Parameter 148.
150 HEAT STAGE3 DIFFER
Heating Stage 3
Differential
0.00 1.50 3.00 °F
Heating stage 3 differential temperat
ure. Used only with room sensor ap
plications.
Differential temperature must be great
er than or equal to Parameter 149.
151 HEAT STAGE4 DIFFER
Heating Stage 4
Differential
0.00 2.00 3.00 °F
Heating stage 4 differential temperat
ure. Used only with room sensor ap
plications.
Differential temperature must greater
than or equal to Parameter 150
152 AUTO CHGOVR DEADBND
Automatic Changeover
Deadband
2.00 3.00 10.00 °F
Minimum autochangeover dead-band
temperature. Dead band must be
greater than or equal to Parameter 142
plus Parameter 143.
Used in room sensor applications.