TABLE 66. PRODIGY 2.0 ALARM CODES
TYPE
ALARM
CODES
Event ActionDISPLAY MESSAGE
TYPE
ALARM
CODES
56 ALARM HEAT 1 CAI SWITCH S18 Check heat section 1 combustion air motor and proof switch.
57 ALARM STRIKE 3 HEAT 1 CAI SWITCH S18 Check heat section 1 combustion air motor and proof switch. Number of occurrences is reached.
58 ALARM HEAT 1 NO PROOF GAS VALVE GV1 Check heat section 1 ignition control, flame proof, gas valve 1 and gas supply.
59 ALARM STRIKE 3 NO PROOF GAS VALVE GV1 Check heat section 1 ignition control, flame proof, gas valve 1 and gas supply. Number of occurrences is reached.
60 ALARM PRIMARY HEAT 2 LIMIT OPEN S99 Check heat section 2 primary burner limit switch to see if it is open. Check air flow, limit switch and wiring.
61 ALARM STRIKE 3 PRIMARY HEAT 2 LIMIT OPEN S99
Check heat section 2 primary burner limit switch to see if it is open. Check air flow, limit switch and wiring. Number of oc
currences is reached.
62 ALARM HEAT 2 LIMIT OPEN S100 Heat section 2 secondary heat limit switch is open. Check air flow, limit switch and wiring.
63 ALARM STRIKE 3 HEAT 2 LIMIT OPEN S100
Heat section 2 secondary heat limit switch is open. Check air flow, limit switch and wiring. Number of occurrences is
reached.
64 ALARM HEAT 2 ROLLOUT OPEN S69 Check roll out sensor and gas supply.
65 ALARM STRIKE 3 ROLLOUT OPEN S69 Check roll out sensor and gas supply. Number of occurrences is reached.
66 ALARM HEAT 2 CAI SWITCH S45 Check heat section 2 combustion air motor and proof switch.
67 ALARM STRIKE 3 HEAT 2 CAI SWITCH S45 Check heat section 2 combustion air motor and proof switch. Number of occurrences is reached.
68 ALARM HEAT 2 NO PROOF GAS VALVE GV3 Check heat section 2 ignition control, flame roof, gas valve 3 and gas supply.
69 ALARM STRIKE 3 NO PROOF GAS VALVE GV3 Check heat section 2 ignition control, flame roof, gas valve 3 and gas supply. Number of occurrences is reached.
70 - 72 RESERVED
73 ALARM NETWORK SENSOR ERROR Check with integrator for refresh rate, network status lights and wiring.
74 ALARM ZONE (ROOM) SENSOR A2
If measurement is out of specified range (including open/short detection) the system will ignore the Zone Temperature
Sensor readings and set the alarm.
If measurement of Zone Temperature Sensor is out of specified range (including open/short detection) the system will
change operating mode to the specified Backup mode (None, Local Thermistor or Return Air temp).
The system will clear the alarm, if zone temperature sensor measurement is detected in specified operating range and
return the system to monitoring the A2 sensor as the primary sensor input.
Check zone (room) sensor and wiring
75 ALARM OUTDOOR TEMPERATURE SENSOR (RT17)
if measurement of the outdoor temperature sensor is out of specified range (including open / short detection, the alarm will
be activated. alarm will automatically clear once in range condition is detected.
Check sensor and wiring.
76 ALARM HUMIDITY SENSOR A91
If measurement is below specified range ( <5 % RH) the system will ignore the Relative Humidity readings. If measurement
is above the specified range( >100% RH) the system will limit the value to 100%.
If measurement of Relative Humidity Sensor is below specified range while the dehumidification mode using RH sensor is
enabled, the system will set an alarm. The system will clear the alarm if Relative Humidity sensor measurement is detected
in specified operating range OR dehumidification mode using RH sensor is disabled.
Check sensor and wiring.
77 ALARM DISCHARGE AIR TEMP SENSOR RT6
if measurement of the discharge air temperature sensor is out of specified range (including open / short detection, the
alarm will be activated. alarm will automatically clear once in range condition is detected.
Check sensor and wiring.