Table 42. Discharge Air Cooling Parameters Summary
Control Parameter DescriptionUnitControl Value
No. DescriptionUnitMax.DefaultMin.
Short
Description
Screen Name
206 DACC RAT RS PRP BND
Discharge
Air Control
Cooling Re
turn Air Re
set Propor
tional Band
1.0 10.0 30.0 °F
Discharge Air Control Cooling return air
reset proportional band.
Also used to reset free cooling set point
(Parameter 159).
207 DACC RS LIMIT
Discharge
Air Control
Cooling Re
set Limit
5.0 10.0 20.0 °F
Discharge Air Control Cooling total reset
limit. This limits the total DACC reset al
lowed.
Also used to reset free cooling set point
(Parameter 159).